Jebel 100KW Three Phase HV Hybrid Inverter
JebelLog in for pricing
Jebel JBL-HYB-80-125K-3PH SERIES inverter, ranging from 80-125kw, compatible with a large range of High voltage batteries. Except ups function, it can also support generator, which makes it long-term power supply.
Key Features
-
IP66 rated enclosure, designed for both indoor and outdoor deployment in harsh environments.
-
Supports 100% 3-phase unbalanced output on both ports (BACKUP & GRID).
-
Integrated 0-export function
-
Sustain 200% rated power overload for 10 seconds
-
Peak shaving and valley filling to enhances grid stability.
-
110% continuous overload rating at sustained operation
Technical Specifications
|
Models |
80K |
90K |
100K |
110K |
125K |
|
Input DC (PV side) |
|||||
|
Max. PV access power |
160kW |
180kW |
200kW |
220kW |
250kW |
|
Max. PV input power |
128kW |
144kW |
160kW |
176kW |
200kW |
|
Max. PV input voltage |
1000V |
||||
|
Nominal input voltage |
600 V |
||||
|
MPP T working voltage range |
180V-850V |
||||
|
Number of independent MPPT/ strings per MPPT |
8/3 |
||||
|
MPPT max. current |
8*45A |
||||
|
Start-up voltage |
200V |
||||
|
Output/Input AC (Grid side) |
|||||
|
Nominal apparent power |
80kw |
90kw |
100Kw |
110kw |
125kw |
|
Max. apparent power |
88kVA |
100kVA |
110kVA |
120kVA |
137kVA |
|
Nominal voltage |
380V/400V |
||||
|
Nominal frequency |
50Hz/60Hz |
||||
|
Rated current |
121A/ 116A |
136A/ 130A |
151A/ 145A |
167A/ 159A |
189A/ 181A |
|
Max. current |
133A |
149A |
166A |
184A |
207A |
|
Power factor |
-0.8~+0.8 (adjustable) |
||||
|
THDi |
<3%(Nominal Output) |
||||
|
Grid system pattern |
3L+N+PE |
||||
|
Max. AC current from utility grid |
300A |
||||
|
Output AC (Back-up) |
|||||
|
Nominal output power |
80kw |
90kw |
100Kw |
110kw |
125kw |
|
Max. output apparent power |
88kVA |
100kVA |
110kVA |
120kVA |
137kVA |
|
Nominal output voltage |
380V/400V |
||||
|
Nominal output frequency |
50Hz/60Hz |
||||
|
Output THDV |
<3% |
||||
|
Automatic switch time |
<10ms |
||||
|
Battery |
|||||
|
Battery type |
Li-ion |
||||
|
Battery voltage range |
200V~800V |
||||
|
Max. charging/discharging current |
2*100A/2*100A |
||||
|
Charging strategy for Li-ion battery |
Self-adaption to BMS |
||||
|
Efficiency |
|||||
|
Max. MPPT efficiency |
99.9% |
||||
|
Europe efficiency |
97.5% |
||||
|
Max. battery to load efficiency |
98% |
||||
|
Protection |
|||||
|
Anti-islanding protection |
Yes |
||||
|
Insulation impedance protection |
Yes |
||||
|
RCD detection |
Yes |
||||
|
PV reverse polarity protection |
Yes |
||||
|
Output over voltage protection |
Yes |
||||
|
Output over current protection |
Yes |
||||
|
General Data |
|||||
|
Dimensions(L/W/H)in mm |
1140/367/820 |
||||
|
Weight |
137Kg |
||||
|
Operation temperature range |
-30℃~60 ℃ |
||||
|
Heat dissipation mode |
Smart cooling |
||||
|
IP Class |
IP 66 |
||||
|
Maximum altitude |
4000m |
||||
|
Self-Consumption night |
<3W |
||||
|
Topology |
Transforerless |
||||
|
Features |
|||||
|
LCD display |
Yes |
||||
|
Communication interface |
WiFi/GPRS/RS485 |
||||
|
Standards |
EN 62109/EN 62477/EN IEC 61000/CEI 0-21/NTS-631/RD647/UNE 217001/ UNE 217002/VDE 4105/IEC 61727/IEC 62116/IEC 61683/EN 50549/G98/ G99/NRS 097/UTE C 15/VDE V 0126 |
||||
- single or three-phase:
- three-phase
- Frequency:
- 50
- Voltage:
- 380
- Battery Voltage:
- 200-800