WECO 5K3-XP HV Box Safety Controller
WECOContact us for pricing
Log in for pricing
HV Box Safety Controller
Basic Parameters | 5K3-XP HV RACK MODULE FOR INDOOR OR CABINET USE ONLY |
Application | String Safety Device |
Operative Voltage | 150/1000 Vdc |
Max Charging Current | 150A/30sec |
Max Discharging Current | 150A/10sec |
Manual Breaker capacity | 125A |
Contactor Capacity | 150A (Peak 250/30sec) |
Pre-Charge Circuit | 150Ohm/4sec (Contactor Max Current 50A) |
Insulation Monitor | Yes |
Max number of modules per string |
17/1000Vdc |
Connector type |
WeCo PLUGS 200A Fast Connection |
Ingress Protection |
IP20 |
Communication Port |
RS485, CAN, 232, Wifi, Bluetooth |
Altitude (m) |
< 3000 |
Protections With HV Box |
HV Box is equipped with 125A Breaker + 150A Contactor + 200A/1000Vdc Fuse Four protection logics for HV Box, Real-time balancing, Adaptive charge/discharge CAN logic, Three steps adaptive charging logic, 2xDI/DO programmable ports, Mobile app for monitoring, control, debugging, firmware update and historical information. Precharge circuit 150 Ohm/4seconds. |
Notes |
See warranty terms for Performance warranty applicability. See Performance Warranty Terms and the Standard Test Conditions ’’STC’’ for operative temperature and standard current. All data is subject to change without prior notice; always ask WeCo for the most recent datasheet and manual before purchasing. No part of this document can be copied or reproduced without written permission of WeCo. HVBox Rack XP Is designed to operate with rack support and indoor |
- Voltage:
- 192-979.2
- Ampere-hour:
- 105
- Warranty:
- 10