Huawei 200KW Smart String ESS
HuaweiContact us for pricing
Log in for pricing
Energy Storage System Parameters
Model Type |
LUNA2000-200KWH-2H1 |
LUNA2000-161KWH-2H1 |
LUNA2000-129KWH-2H1 |
LUNA2000 -97KWH-1H1 |
Battery Configuration |
12S1P |
10S1P |
8S1P |
6S1P |
Maximum battery capacity of the energy storage system |
193.5kWh |
161.3kWh |
129.0kWh |
96.8kWh |
Max. Charging Power |
100 kW |
|||
Max. Discharging Power |
≤100 kW |
≤100 kW |
≤100 kW |
≤92 kW |
Dimensions (W x H x D), including Smart Rack Controller and Smart PCS |
1810mm×2135mm×1200mm |
|||
Dimensions (W x H x D) |
2570mm x 2135mm x 1200mm |
|||
Weight (including the battery module) |
≤2950kg |
≤2690kg |
≤2430kg |
≤2170kg |
Weight (without the battery module) |
≤1070kg |
≤1070kg |
≤1090kg |
≤1130kg |
Operating temperature range |
-30 °C ~ 55 °C |
|||
Storage temperature range |
-40 °C ~ 60 °C |
|||
Operating humidity range |
0 ~ 100% (non-condensing) |
|||
Maximum operating altitude |
4,000 m |
|||
Installation Environment Requirement |
Outdoor installation |
|||
Battery temperature control mode |
Industrial-grade air conditioner |
|||
Fire suppression of energy storage system |
YES |
|||
Auxiliary Power Supply |
220Vac,≤4.2kW |
|||
Communication port |
Ethernet / SFP |
|||
Communication protocol |
Modbus TCP |
|||
Protection degree |
IP55 |
|||
EMC Protection Rating |
ClassA |
|||
DC Lightning Protection |
Type II |
Standards
Environment |
RoHS6 |
Certification Standards |
GBT 36276-2018;IEC62619; UL9540A;UN38.3; |
- Voltage:
- 350-691.2
- Ampere-hour:
- 280