WECO 5KW Dual Voltage Battery
WECOLog in for pricing
DUAL VOLTAGE 5K3-EVO
Features:
- State-of-the-art heating system keeps battery cells above minimum temperatures, ensuring consistent performance even in persistently
cold conditions. - Safety always come first! Each module comes equipped with a sophisticated fire suppression system, offering unparalleled safety and peace of mind.
- Parallel up to 105 Modules.
548 kWh.
Total 8 clusters of 15 batteries.
626 kWh. - Min 2 Modules + HV BOX
Max 17 Modules /1000Vdc.
Total 8 clusters of 17 batteries
710 kWh.
Datasheet :
Module Capacity(kWh) |
5,22 |
Single Module Nominal Voltage (VDC) |
51.2 |
Application |
Dual Voltage |
Modules Expandibility |
LV Mode: Max 15 Modules in Parallel / 105 with HUB LV HV Mode: 17 in series / 170 with HUB HV |
Voltage Range (VDC) |
47,5-56.8 |
Capacity (Ah) |
102 (Cell Capacity 108 Ah) |
Usable Capacity(Wh) |
5220 Wh |
Dimensions (mm) |
680 * 440 * 160 |
Weight (kg) |
50 |
Charge / Discharge Peak(A) |
100 |
Recommended Working Conditions |
0.5C 80% DoD |
DoD |
Up to 98% |
Communication Port |
RS485,CAN,RS232 |
Communication Accessories (For Master Only) |
Wi-Fi / Bluetooth Dongle |
Modules in Series Connection |
Up to 17 Modules and up to 10 clusters in parallel |
Modules in Parallel Connection |
Up to 15 Modules and up to 7 clusters in parallel |
Discharge Temperature (°C)** |
-20 ~+60°C |
Charge Temperature (°C)** |
-10 ~ +55°C |
Shelf Temperature (°C)** |
0 ~+ 45°C |
Humidity (%) |
5 ~ 95% |
Elevation(m) |
< 3000 |
Design Life |
10 Years (25°C) |
Expected Life Cycles EOL 80% |
> 7000(25°C) |
Standards |
IEC62619;UL1973;CE;IEC 61000;UN38.3; |
Features |
Auto BalancingBMS, 16 Channels Equalizer, Module Local Monitoring. |
Protections | Fuse: 150 A / 60 VDC Contactor150A/60vdc |
Notes |
Real-time Balancing, AdaptiveCharge/DischargeCAN Logic, Three Steps AdaptiveChargingLogic, 2xdi/DO ProgrammablePorts, Mobile App For Monitoring, Control, Debugging, Firmware Update, And HistoricalInformation. |