Solis Smart Meter with Analysis Function for S3/G3 Logger for Zero Export
SolisLog in for pricing
The UMG 96RM multifunctional meter is primarily designed for use in low-voltage and medium-voltage distribution systems. The device measures harmonics currents up to the 40th harmonic and has rotating field components. The device only has 2 digital outputs. It has no digital inputs and no measurement data storage.
General |
|
Net weight |
265 g |
Net weight (with attached connectors) |
300 g |
Device dimensions |
approx. l = 42 mm, b = 97 mm, h = 100 mm |
Service life of the backlight |
40,000 hours (50% of initial brightness) |
Transport and storage The following information applies for devices that are transported or stored in their original packaging. |
|
Free fall |
1 m |
Temperature |
K55 (-25 °C to +70 °C) |
Relative humidity |
0 to 90% RH |
Ambient conditions during operation |
|
The UMG 96RM is intended for use in weather-protected, fixed locations. Protection class II according to IEC 60563 (VDE 0106, part 1). |
|
Rated temperature range |
K55 (-10 °C .. +55 °C) |
Relative humidity |
0 to 75 % RH |
Operational altitude |
0 .. 2000 m above sea level |
Degree of pollution |
2 |
Installation position |
any |
Ventilation |
Forced ventilation is not required. |
Foreign body and water protection - Front - Back - Front with seal |
IP40 according to EN60529 IP20 according to EN60529 IP54 according to EN60529 |
Power supply voltage |
||
Option 230V |
Nominal range |
90V - 277V (50/60Hz) or DC 90V - 250V; 300V CATIII |
|
Power consumption |
max. 7.5VA / 4W |
Option 24V |
Nominal range |
24V - 90V AC / DC; 150V CATIII |
|
Power consumption |
max. 3.5VA / 2W |
Operating range |
+-10% of nominal range |
|
Internal fuse, not replaceable |
Typ T1A / 250V/277V according IEC 60127 |
|
Recommended overcurrent protection device for line protection (certified under UL) |
Option 230V: 6 - 16A Option 24V: 1 - 6A (Char. B) |
Recommendation for a maximum number of devices on a circuit breaker:
Option 230V : Circuit breaker B6A: max. 4 devices / Circuit breaker B16A: max. 11 devices
Option 24V : Circuit breaker B6A: max. 3 devices / Circuit breaker B16A: max. 9 devices
Connection capacity of the terminals (power supply) Connectable conductor. Only one conductor may be connected per contact point! |
|
Single-wire, multi-wire, finely stranded conductor |
0.2 - 2.5mm2, AWG 26 - 12 |
Pin terminals, ferrules |
0.2 - 2.5mm2 |
Tightening torque |
0.4 - 0.5Nm |
Stripping length |
7mm |